Ecoflam Burners

DUAL MULTICALOR

Main features

  • Aluminium casing up to Multicalor 200.1 and steel casing from 300.1 with electrical panel integrated on the burner.
  • Adjustable combustion head for fine tuning / matching with different shapes of combustion chamber.
  • Gas pilot from Multicalor 170.1.
  • Hi - Low version with electric servomotor and integrated system for the regulation of air gas and light oil with two nozzle from Multicalor 45 to Multicalor 300.1.
  • Progressive version with electrical servomotor and double adjustable mechanical cam that allows air gas/light oil fine tuning.
  • Progressive version with electrical servomotor and double adjustable mechanical cam that allows air gas/light oil fine tuning.
  • Progressive or modulating nozzle with flow and return. Shut down flow system on the nozzle managed by coil from Multicalor 700.1.
  • Firing head with adjustable primary air system that changes according to output required.
  • Easy maintenance with sliding bars system.  Standard from Multicalor 700.1 and on request from Multicalor 300.1.
  • Standard version running on manual fuel selection mode and on request automatic fuel changeover. The automatic change over system can be triggered by gas pressure or by a timer.
  • Special version for all type of applications and fuel charachteristics on request.
  • Duoblock range 180 - 25000 kW.

Technical data


Models
Output max
Output min
Flow rate max
Flow rate min
Power supply
Motor
Operation
 
kW
kcal / hx1000
kW
kcal / hx1000
kg/h
kg/h
V
W
 
Dual 1
40
34,4
23
19,78
3,37
1,94
230/400
0,05
ON-OFF
DUAL 2
65
55,9
34
29,24
5,48
2,86
230/400
0,05
ON-OFF
DUAL 3-3P
110
94,6
58
49,88
9,27
4,89
230/400
0,2
ON-OFF / P
DUAL 4 
200
172
110
94,6
16,86
9,27
230/400
0,25
ON-OFF
DUAL 4 P  
200
172
100
86
16,86
8,43
230/400
0,25
P
DUAL 5 P
345
296,7
110
94,6
29,1
9,27
230/400
0,3
P
MULTICALOR 45 
500
430
190
163,4
42,17
16
230/400
0,55
AB
MULTICALOR 45 
500
430
120
103,2
42,17
10,12
230/400
0,55
PR-MD
MULTICALOR 70 
700
602
250
215
59
21
230/400
0,74
AB
MULTICALOR 70 
700
602
190
163,4
59
16
230/400
0,74
PR-MD
MULTICALOR 100 
1.000
860
300
258
84,31
25,3
230/400
1,1
AB
MULTICALOR 100 
1.000
860
200
172
84,31
16,86
230/400
1,1
PR-MD
MULTICALOR 140 
1.300
1.118,00
400
344
109,6
33,7
230/400
2,2
AB
MULTICALOR 140 
1.300
1.118,00
250
215
109,6
21,08
230/400
2,2
PR-MD
MULTICALOR 170.1
1.770
1.526,00
342
295
150
29
230/400
3
AB-PR-MD
MULTICALOR 200.1
2.150
1.853,45
414
356,9
182
35
230/400
4
AB-PR-MD
  • Fuel: Natural Gas (L.C.V. 8.570 kcal/Nm3), LPG (L.C.V. 22.260 kcal/Nm3)
 
DUAL MULTICALOR
DUAL MULTICALOR
© 2009 Ecoflam Bruciatori spa. All rights are reserved.
Legal headquarters: 31023 Resana (TV) Via Roma 64
VAT n: 00879740264 - Reg. Imprese Treviso - Cap EUR 3.690.000.
Company subject to the direction and the coordination of Ariston Thermo Spa